HVAC Motor Not Starting or Running Slowly? Rotom Run Capacitor 36-2-370440 - Restore 2MFD Motor Run Capacitance
A defective motor-run capacitor is one possible cause of fan motor or blower motor starting and running problems in HVAC systems. The single-value run capacitor maintains the phase shift needed to keep the motor running efficiently. When it fails, the motor may hum, struggle to reach operating speed, run hot, or shut off on thermal overload.
Common service component in residential and light-commercial HVAC fan motors and blower motor applications.
Part 36-2-370440 is the Rotom specification-based replacement rated at 2MFD and 370/440 VAC that may restore proper motor-run support when testing confirms the original capacitor is defective and no related motor or electrical fault remains.
Is This the Right Part?
Confirm MFD, Voltage, Shape and Dimensions before ordering. This is the correct specification match if ALL of the following are true:
- Your original capacitor is rated exactly 2MFD - capacitance must match exactly
- Your original capacitor is rated 370V or 440V - a 440V replacement may replace a 370V original; the reverse is not permitted
- Your application uses a single-value oval run capacitor - not a dual-run capacitor and not a start capacitor
- Your mounting space accommodates an oval body approximately 2.03in wide, 1.24in deep and 1.58in high
Not sure? Send us your capacitor label specs - we will confirm before you order.
Common Symptoms of a Failed Motor-Run Capacitor
- Fan or blower motor hums but fails to start
- Motor starts slowly or struggles to reach full operating speed
- Motor runs hot or trips on thermal overload
- Capacitor body visibly bulged, leaking, or reads out-of-tolerance on a capacitance meter
If these symptoms match and capacitor testing confirms a defective reading, this is a likely failed component. Similar symptoms may also result from wiring, a contactor, motor winding failure, or electrical-supply problems - confirm the capacitor is the root cause before ordering.
Part Details
- Part Number: 36-2-370440
- Brand: Rotom / AllTemp - New
- Type: Oval Single-Value HVAC Motor-Run Capacitor
- Capacitance: 2MFD / 2 uF
- Voltage Rating: 370/440 VAC (dual-voltage)
- Shape: Oval
- Width: 2.03 in
- Depth: 1.24 in
- Height: 1.58 in (compact - verify available mounting height)
- Features: Built-in interrupter, UL and cUL Recognized
- Availability: In Stock
- Compatibility: Specification-based - match capacitance, voltage, shape, and dimensions to original
Also Replaces These Part Numbers
Direct oval replacements (2MFD, 370/440V, oval):
12026 (MARS Blue Box), 12926 (MARS/JARD), 14026 (MARS USA), POCF2A (Titan HD), POCF2 (Packard/Titan), TOCF2 (Titan Pro), CR2X440 (Supco), 45020H (DiversiTech), 27L1021 (Genteq/Capcom), 27L1021BX (Genteq/Capcom), C402 (Capcom/Genteq), C402L (Capcom/Genteq), OCF2 - electrical rating and oval configuration match; case height varies. The Rotom case is approximately 1.58in high; some equivalents are 2.0 to 3.0in high. Confirm mounting strap size, available height and terminal clearance before ordering.
Electrical equivalents - different case shape (confirm mounting fit before ordering):
14102 (MARS USA, round), 36-2S440 (Rotom, square plastic, 250-440V), 12382 (MARS mini-split, square, 450V) - electrically equivalent; not mechanical drop-in replacements for the original oval bracket. A replacement mounting method may be required. Do not leave a capacitor unsecured inside the equipment.
Inspect the contactor while the unit is open and replace it only when testing or visible damage (pitting, burning) confirms it is defective. A worn contactor is a common co-failure with a run capacitor in aging HVAC units - addressing both at the same service call avoids a repeat visit.
Installation
Skill Level: Advanced - Qualified HVAC Technician Required. Disconnect and lock out all power before opening the electrical compartment. HVAC capacitor diagnosis and replacement should be completed by a qualified technician. Photograph the original wiring before disconnecting. Connect the replacement to the same terminals and confirm all connections are secure before restoring power and testing motor operation.
Specification Compatibility
This capacitor is compatible with any HVAC motor application that requires an oval single-value run capacitor rated at exactly 2MFD and 370V or 440V, provided the oval body (2.03in wide x 1.24in deep x 1.58in high) fits the existing mounting bracket. Compatibility is determined by electrical specification and physical fit - not by equipment model number. Contact us with your original capacitor label before ordering if you are unsure.
Pro Tip
At 1.58in high, the Rotom 36-2-370440 is one of the more compact 2MFD oval capacitors available. If ordering a cross-reference equivalent from another brand, verify the case height against your available mounting space - some 2MFD oval capacitors from other manufacturers are 2.0 to 3.0in high and may not fit the original bracket without modification.
✅Compatibility & Cross Reference
Not sure about your model number? Call 1-877-899-7278 and we’ll help you confirm. All brand names are the property of their respective owners and are used for compatibility reference only.
Buy Online Pick Up In-Store
Kitchener, Ontario N2E 1W8
- Choosing a selection results in a full page refresh.